Redline
D.34
Comfort functions
A
B
C
D
E
F
G
X
Function
Priority relays offer the possibility to
limit the energy consumption
in installations with a defined
maximum power. This limitation is
getting measuring the installation
total current continuously and in the
case consumption would be higher
then fixed value, priority relay would
disconnect the non-priority load.
Series PR
Applications
In some installations the maximum power is limited by the contracted power
with the electricity company. If this contracted power is surpassed, the main
MCB of the installation opens. Priority relays are used in order to avoid the
opening of the main MCB.
A similar case, for exemple, would be an installation where new loads would
be added without changing the installation (cable sizes, MCB’s...). In this
case a priority relay will be installed before the non priority load that would
be disconnected when the contracted or limited power is
surpassed. Priority... disconnected. The priority relay will realise that the
installation total load will come back to be lower than its..., the non priority
load will come back to be connected.
Characteristics
Priority relay can work in nets with nominal power of 6 kW if we make a
direct connection or higher if we use a current transformer to connect the
priority relay to the net. In each case priority relay could be able to
disconnect loads with a nominal power from 0 to 6kW or from 0% to
100% when current transformer is used.
Standard/Marking
IEC 61095
Priority and sequence phase relays
Performance
Priority Relay Series PR
Nominal Voltage Un 230V
Maximum nominal current 32A direct, 5A with current transformer
Nominal current 2...32A
Compact capacity Pozidriv 1/2x2.5mm
2
or 1x6mm
2
Contact type NC or NO
Work temperature -20...+55°C
Work area 0 to 7 kW
Fixed delay time 0.5sc
Isolation tension (contact-coil) 2.5 kV
Isolation class II
IP IP20
Electrical endurance 100,000 ops.
Mechanical endurance 1,000,000 ops.
Maximum changeover frequency 750 ops./h